Hardware for Each Remote Station:
Analog Input Module- Resolution : 16bit
- Input Channel : 8 differential
- Sampling rate : 10Hz
- Voltage Input : +/-150mV, +/-500mV, +/-1V,
+/-5V,+/-10V
- Current input : +/-20mA
- Isolation Voltage : 3000V
- Dual Watchdog Timer
- Over Voltage Protection : +/-35V
Digital Output Module- Output Channels : 8
- Isolation with common power
- Isolation Voltage : 3750Vrms
- Load Voltage : Max +30V
- Max Load Current : 375mA
- Input Channels : 4
- Digital Level 0 : 1V Max
- Digital Level 1 : 4 to 30 V
- Input Impedance : 3k ohms
- Power Input : +10 to +30 VDC
- Power Consumption : 1.7W
RS-232 to RS-485 Converter- RS-232 Interfaces are full-duplex and require just data signals
- Signals : TX, RX
- Baud Rates : Std Windows rates upto 115.2
kbaud
- Data Bits : 7 or 8 bits
- Parity : None, odd or even
- Stop bits : 1 or 2
- Flow Cntrol : None
- RS-485 Interface is half-duplex and includes self tuner and
network protection
- Signals : TX/RX pair
- Baud Rates : Std Windows rates upto 115.2
kbaud.
- Data Bits : 7 or 8 bits
- Parity None : odd, or even
- Stop bits : 1 or 2
- Distance : 1200 M
Physical- Size : 123mm x 72mm x 33 mm (without
mounting bracket)
- Display : Single LED standard, 5 digit LED
display optional
- Connectors : RS-232 -DE-9 Female RS-485 &
Power- Screw terminals for 16 to
26 AWG wires.
| Environmental |
- Temperature : Operating -25 °C to 75 °C
Storage -40 °C to 85 °C
- Relative humidity : 0 to 90% (not condensing)
- Power consumption : 2.2 W @ 10 to 30 Vdc
| GUI BASED WINDOWS COMPATIBLE SOFTWARE |
VPL DCS is an interactive software that displays the data
received from the remote stations. All the three remote stations
are named as STATION1, STATION2, STATION3.
Each remote station’s data is displayed in the software under
the heading of STATION1, STATION2 & STATION3.
| ORDERING INFORMATION |
- VPL-DCST-2 - DCST with two remote stations
- VPL-DCST-3 - DCST with three remote stations
| | |